I. Product Overview

HZJB-1600B relay protection tester is designed according to the relevant technical specifications of "DL/T 624-2010 Technical Conditions for microcomputer relay protection test Device", and based on the IEC61850 communication standard system, using advanced computer technology to realize the relay protection test device.

Equipped with high-performance power amplifier and based on the powerful PowerPC+X86 platform, the product adopts modular design, with powerful, high precision, small size, light weight characteristics, can realize the function and performance of the relay protection device, measurement and control device test, suitable for power plants, substations, all kinds of scientific research units and equipment manufacturing enterprises

II. Special Functions

Ø Unique parallel computing and communication bus technology

“HZJB-1600B Relay Protection Tester”Hardware architecture has high-precision clock synchronization technology, in the case of multiple cascades through the internal clock synchronization technology can ensure ±20ns error, through high-precision clock synchronization tuning and unique software communication bus, so that multiple instruments in the precise time range can be synchronized output, to achieve the cascade test of multiple instruments. The cascading method can effectively improve the number of interfaces and test scale of the test system, and is suitable for multi-branch test, substation simulation and other large-scale tests and tests.

Ø Intelligent read and write protection device information

“HZJB-1600B Relay Protection Tester”firstly integrate the MMS protocol into the test system, which realizes the real-time automatic reading and writing protection device setting, test parameters setting, soft pressure plate of the drop device to match the current test project, and automatically completes the whole test process. This technology is the key technology of automatic testing.

Ø Manual test and automatic test dual mode

Manual test

“HZJB-1600B Relay Protection Tester”provides a variety of general test modules, protection test modules and special test modules, providing perfect test solutions for various types of secondary equipment in substation, including relay protection devices and other safety automatic devices. At the same time, it adopts the engineering configuration interface and configuration process similar to the intelligent substation SCL configuration tool, which conforms to the testing habits of the operators, and provides various types of graphics and forms for displaying the test progress and test results, greatly improving the efficiency of the test.

Automatic test  

“HZJB-1600B Relay Protection Tester”adopts template-based management scheme to manage automatic test solutions. A test template can contain multiple test items. Each test template is configured for a type of protection. After the template configuration is complete, the user does not need to perform other manual settings, and can complete the automatic test of all test items with one key click Start, and automatically give the test results. Because it is a test template configured for a certain protection device, the template can be used for automatic testing of other types of protection without reconfiguration, improving the reuse rate and test efficiency of the automatic test template.

III. Technical Characteristics

Intelligent test module

Support intelligent test template editing, test items can be added arbitrarily during the test process, and saved as reusable test engineering files, improve the test efficiency in the later inspection and elimination stage.

Automatic test

With local protection and digital protection automatic test function, can complete all the test items of a single protection device with one click.

Analog output

Tests can be carried out on simulated protection, transformer group and other devices.

Multiple scan modes

Support testing amplitude, phase, frequency, impedance, vector, sequence, power according to the manual or automatic ways, and support automatic change test according to the gradual, slip, comprehensive ways;

Security and alarm

With overheating and over-current protection function, the current source has open circuit protection function and open circuit alarm function, the voltage source has overload and short circuit protection function;

Fault replay

Supports fault simulation and data playback in COMTRADE format;

MMS Service

With MMS set value read and write function, can read and write intelligent IED device set value and other configuration information

Time synchronization and Time service

With synchronous trigger function, support direct access to GPS/BD antenna for timing, also support the IRIG-B, PPS and PTP 1588 timing mode and can support the output of IRIG-B, PPS and PTP 1588 timing signals.

Hard contacts open in and out

The open quantity is active and passive adaptive contact, the input type and input voltage are identified automatically, the channels are isolated each other, and the polarity reverse connection has warning;

State sequence

  There are 12 analog channels, and the state sequence can achieve 120 groups (measured by the lower computer). The upper computer software analog channels have no upper limit.

Waveform playback

  Support recording data playback, continuous playback in the form of recording folders, support waveform expansion playback.

Touch operation

It is equipped with 10.4 inch high resolution display and supports touch operation.

Wireless connection

Provide 4G remote test function, with WiFi module, easy to use.

IV. Main Technical Parameters

Power supply

Power dissipation     <2000VA

Ac power supply 220V±20%4763Hz

Dc power supply 200380 VDC

AC voltage source output

Measuring range   6×125 V125V/60VA per channel

Accuracy   0.2~2V±2mV2V~130V±0.05%

Resolution   1mV

AC voltage source output

Measuring range   6×30A30A/300VA per channel       

Accuracy   0~500mA±1mA500mA~30A±0.05%

Resolution   1mA

Output phase

Range   0~360°

Accuracy   ±0.1°

Resolution   0.1°

Output frequency

Range    0~1200Hz

Accuracy   <±0.001Hz(0~65Hz)   <±0.02Hz(450~1200Hz)

Resolution   0.001 Hz

DC voltage source output

Range   -175+175VL-N),1*0350VL-L);

Accuracy   0.1%

DC voltage source output

Range   6 channels each 0~30A/250VA

Accuracy   0.1%

Independent auxiliary DC

110/220VDC is switchable, power no less than 100W, Precision0.5%

Synchronous interface

NumberGPS/BD ANT 1 pieceIRIG-B/PPS optical signal 2 pieces:1 time synchronization and 1 time serviceIRIG-B/PPS  signal 2 pairs1 pair time synchronization and 1 pair time serviceIEEE 1588 1 pair

Interface typeGPS/BD ANT,IRIG-B/PPS optical signalIRIG-B/PPS electric signalIEEE 1588

Time measurement

Range1ms~9999.999s

Accuracy1ms

Digital Input

Number8 pairs     

Digital Output

Number 6 pairsamong them, 2 pairs are fast opening (reaction time ≤0.1ms), which can be added.

Interrupting capacity DC250V /0.5A

Wireless connections

Interface typeWIFI4G

Wired connection (Ethernet communication interface)

Number of ports 2

Interface type100 megabit LAN portRJ45

Power supply

Supply voltage AC/DC 220VTolerance error±20%

Power supply frequency47~65 Hz

Auxiliary power supply 110V/220V each channel

Analog small signal input (optional)

Number of channels: 12;

Interface type: Aviation plug, AC voltage

Analog small signal output (optional)

Analog small signal output (optional);

Interface type: Aviation plug, AC voltage

USB Interface

Number3

Working environment conditions

Operating temperature-10℃~50℃

Humidity ≤95%,No condensation

Others

Weight18.5kg(The light chassis is 10.5KG. The switch output is 4 pairs and the input input is 8 pairs. Other parameters do not change.)

Size460×436×212(mm)

On-line interfaceRJ45

Display screen10.4 inch 1024768 true color LCD with touch function