HZJB-II Single Phase Relay Tester, Relay Test Equipment
HZJB-II Single Phase Relay Tester, Relay Test Equipment
Single Phase Protection Relay Test Kit
Single Phase Secondary injection test set
Single phase Relay Testing
Single Phase Protective Relay Testing Equipment

I. General 

    HZJB-II Single Phase Relay Protection Tester is a portable field testing equipment with excellent performance; Elegance and polished appearance with aluminum alloy chassis and PC panel, within the ARM chip control, LCD screen display voltage and current output stopwatch, it could output a full isolation way for adjustable AC/DC voltage, and AC/DC current and a way for adjustable DC voltage; the output loop with double overload protection with large output capacity ,small volume, light weight, high reliability ,It Suitable for field calibration and test for various relay.

II. Main Features

1.Output a full isolation way for adjustable DC voltage, Automatic protection for short circuit, overload and out range.

2.Maximum Output Current:0~150A.

3.Equipped with LCD digital AC/DC volt-ampere meter, can show the AC and DC voltage and current values, stopwatch, potential, contact state.

4.Internal electric stopwatch; Available electrical contacts, maximum potential  250V; Dual channel measurement.

5.Light-weight design, small-volume, and fully-functional.

III. Main Technical Parameter And Functions

1.Rated input power: AC:220V±10%·1000VA·50Hz  

2.AC Output

Range(A)

No-load Voltage

 (Minimum)V

Full-load Voltage

(Minimum)V

Full-load Current

 (Maximum)A

0~10

90

80

10

0~40

25

22

40

0~100

10

8

150

Range(V)

No-load Voltage

 (Minimum)V

Full-load Voltage

(Minimum)V

Full-load Current

 (Maximum)A

0~250(AC)

250

240 

3

0~300(DC)

320

250

3

3.DC auxiliary Output

Range V

Voltage V

Maximum current A

0~110

120

0.5

110~220

220

0.5

4.Stopwatch:

Range: 0.0000~999999S,Resolution: 0.1mS,

Accuracy: ±5

With electrical contacts and potential input, the maximum input voltage: DC 250V

5.Ammeter:

Range: internal: 0.000~150.0A;

External: 0.000~6.000A(AC or DC)

Accuracy: 0.5%, Measurement methods: AC: True RMS value DC: Average

6.Voltmeter:

Range: 0.0~600.0V(AC OR DC);

Accuracy: 0.5%, Measurement methods: AC: True RMS value DC: Average

7.Resistors and Capacitors:

Resistance: 0.5 ohm to 2.5k ohm

Capacitor: 10uF, maximum voltage AC 450V

8.Division / combination of auxiliary contacts

Maximum current: 1A, Maximum voltage: AC250V or DC120V

9.Using Environment: Temperature: -10 ~ 40 ℃,

Relative humidity must less than 80%

10.Volume: 320mm×260mm×230mm

11. Weight: 16kg