1. Product technical parameters
Model: HZLY-100A
Nominal flow: 6000L/h
Net oil capacity: 100L/min
Pumping rate: 540M³/h
Ultimate vacuum degree: ≤5Pa
Working pressure: ≤0.5Mpa
Working oil temperature: 20~80℃
Working power supply: 50Hz380V three-phase three-wire
Heating power: 60KW (separately controlled in two groups)
Total power: 67KW
Operating noise: ≤75dB(A)
Inlet/outlet flange: DN40
Vacuum interface flange: DN40
Dimensions: 175×155×190cm
Equipment weight: 820Kg
Continuous working time: ≥200 hours
Average trouble-free working time: ≥5000 hours
2. Product net oil index
oil to be treated
Breakdown voltage: >30kV (ball pole);
Water content: ≤50ppm;
Air content: ≤10% (volume ratio);
after a process
Breakdown voltage: >60kV (ball pole);
Water content: ≤10ppm;
Air content: ≤0.2% (volume ratio);
After three-four processes
Breakdown voltage: >70kV (ball);
Water content: ≤5ppm;
Air content: ≤0.1% (volume ratio);
Acetylene content: 0
3. Product function introduction
◇Remove moisture from oil.
◇Remove gas dissolved in oil.
◇Remove solid particles in oil.
◇On-site oil treatment of transformers and vacuum drying of electrical equipment.
◇On-site hot oil circulation drying is performed on the transformer.
◇After the oil is treated, the 20-60m3 transformer can be oiled under vacuum conditions.