在线客服系统
Huazheng Electric Manufacturing (Baoding) Co., Ltd.
PRODUCTS
HZ-3150A 50A Transformer DC Winding Resistance Tester
HZ-3150A 50A Transformer DC Winding Resistance Tester
HZ-3150A DC Resistance Tester Transformer winding Resistance test equipment automatic three phase transformer winding dc resistance tester
Transformer Winding DC Resistance Tester
50A Transformer DC Winding Resistance Test Set
Factory Price 50A Transformer DC Resistance Tester
Power transformer winding resistance tester 50A

I.Overview

   Transformer DC resistance is the required test item of semi-finished products, finished products factory test, installation, overhaul, change after the tap switch, handover test and power department preventive test in transformer manufacturing.It  can check the welding quality of the winding joint and whether the winding has an inter-turn short circuit, which can detect whether the each position contact of the voltage tap switch is good, whether the actual position of the tap switch is consistent with the indicated position, whether the lead line is broken, whether the multiple wire and winding is broken, etc.In order to meet the needs of the rapid measurement of the transformer DC resistance. The 3150A DC resistance tester is developed by our company.The instrument uses a brand-new power supply technology, with a small volume, light weight, large output current, good repeatability, strong anti-interference ability, perfect protection function and other characteristics.The whole machine is controlled by a high-speed micro controller, with a high degree of automation, with automatic discharge and discharge alarm function.With high accuracy and simple operation.It can rapidly measure the direct resistance of transformer.

 

II.Technical indicators

Item

Technical indicators and parameters

Remarks

Test current

<20mA2.5A5A10A20A50A


 

 

 

Measuring range

40μΩ400mΩ  50A

100μΩ1Ω    20A500μΩ2Ω    10A

1mΩ4Ω       5A

  2mΩ8Ω       (2.5A)        

accuracy±(0.2%+2)

10Ω-20KΩ      <20mA

accuracy±(0.5%+2)

Minimum resolution

0.1μΩ


Display

LCD

The resistance shows a valid number of 4 digits

Data storage

1000 Groups


Work environment

Ambient temperature: 0℃ ~40℃ relative humidity: <90%RH, no dew condensation


Power supply

AC 220V±10V50Hz±1 Hz

Insurance Tube, 10A

Maximum power dissipation

1000W


Outline dimension

Main engine405×230×355mm

Line box360×260×180mm


Weight

Main engine15.1KG

Line box: 5.75KG


Test line length

Standard configuration13 meters

Length can be optional