I. Introduction
Contact Resistance Tester , also known as micro-ohmmeter and contact resistance tester , is specially developed by our company to measure the contact resistance of various high-voltage switches, high-voltage circuit breaker contact resistance, connection resistance of metal welding components, metal conductor loop resistance, Meter of precision micro-ohm resistance.
This instrument takes high-speed microcontroller as the core , combines high-precision A/D converter , digital measurement technology, anti-power frequency interference technology , and advanced program- controlled current source technology, so that the built-in large-capacity rechargeable lithium battery produces no ripple. DC current, the maximum output is 220A, and the output current can be fine-tuned every 2.5A steps, up to 87 current gears, to meet the multi-current gear test; at the same time, you can set the time ( 10s, 20s, 30s, 40s, 50s, 60s ) Continuously output large current test, can test with high precision , high stability , and high intelligence in strong interference environment ; in circuit design , it has functions such as open circuit protection and overheat protection .
The instrument adopts 5.6-inch color LCD display, Chinese and English operation interface, which is clear and intuitive; it is also equipped with standard resistors, and the accuracy of the instrument can be self-checked before the formal test; the instrument has wide measuring range , large data storage capacity, strong anti-interference ability, and simple operation , Handheld, small size, easy to carry, etc. It can also be equipped with a printer for data printing.
II. Technical Specifications
Function | Various contact resistance tests of high-voltage switches and high-voltage circuit breakers; connection resistance tests of metal welding components; various circuit resistance tests of metal conductors ; precision micro-ohm resistance tests | |
Power supply | Built-in: 12.6V 9000mAh rechargeable lithium battery | |
Test method | Four-wire method | |
Charger | 12.6V/2A charger | |
Display mode | 5.6-inch industrial-grade high-brightness color LCD screen | |
Test interface | I+ (current positive), I- (current negative), U+ (voltage positive), U- (voltage negative) | |
Current output | Coarse adjustment gear : ≤ 5 A , 1 0A , 3 0 A, 50 A , 8 0A , 1 00 A, 200A, 220A | |
Thin strip gear: step value 2.5A, up to 87 gears | ||
Range (Built-in battery) | ≤ 5A : | 1mΩ ~3 500mΩ |
10A : _ | 0.1μΩ ~200m Ω | |
30A : | 0.1mΩ ~20mΩ | |
50A : | 0.01mΩ ~15mΩ | |
80A : | 0.01mΩ ~10mΩ | |
100A : | 0.01μΩ ~ 5 mΩ | |
200A : | 0.01μΩ ~6 00u Ω | |
220A: | 0.01μΩ ~5 00u Ω | |
Minimum resolution | 0.01μΩ | |
Test accuracy | Current: 30A~220A ±(reading×0.1%+range 0.2%+1μΩ) Current: 1 0A or ≤ 5A ± (reading × 0.5% + range 0.2% + 10μΩ) | |
Testing time | ≤ 100A: fast (recommended), 10s, 20s, 30s, 40s, 50s, 60s > 100A : fast | |
Printer | Yes (optional), press the print button to print the test results | |
Data storage | After the test is completed, the data is automatically saved and cyclically saved, and 999 sets of data can be stored | |
Meter size | Approx. 188mm(L)×85mm(W)×312mm(H) | |
Package size | Approx. 550mm(L)×420mm(W)×215mm(H) | |
Quality | Instrument mass: about 2.2kg | |
Total mass: about 9.3kg | ||
Test line | Standard length: 3m (optional 5m) | |
The test line is tapped at both ends of the current and voltage , the wiring is simple, and the resistance is less than 10mΩ | ||
Data deletion | Select the format memory option in the setting interface to delete all data | |
Data review | Enter the data query interface, press the up, down, left, and right keys to browse the stored data | |
Automatic shut-down | When using battery power, it will automatically shut down after about 15 minutes of no operation after power on | |
Battery voltage | There is a battery power indicator on the upper right corner of the meter. When the symbol " " is displayed, it means that the battery power is exhausted, and the meter will automatically shut down. Please charge it in time | |
Backlight | The backlight can be set to high, medium and low brightness | |
Working current | The working current is 230mA in non-test state | |
The working current can be set by yourself in the test state | ||
Circuit protection | With open circuit protection, overheat protection, etc. | |
Temperature protection | The instrument is equipped with temperature monitoring | |
Working temperature and Humidity | -10℃~50℃; below 90%RH, no condensation | |
Storage temperature and humidity | -10℃~60℃; Below 70%RH | |
Charging voltage | 12.6V | |
Suitable for safety regulations | IEC61010-1, CAT Ⅲ 600V, pollution degree 2, JJG724-1991 "Verification Regulations for DC Digital Ohmmeter", JJG166-1993 "Verification Regulations for DC Resistors", "DL/T967-2005 Contact Resistance Tester and DC Resistance Fast Tester Verification Regulations" |