I.Testing object
AC withstand voltage test of 22kV/600MW thermal power generator, capacity ≤0.2158uF, test frequency 50Hz, test voltage 47kV, test time 1min
II.Main technical parameters and functions
1. Rated capacity:200kVA;
2. Rated voltage:50kV;
3. Rated current:4A;
4. Operating frequency:power frequency 50Hz;
5. Output voltage waveform distortion rate:≤0.5%;
6. Allow continuous working hours:5min(under rated load);
7. Temperature rise after continuous operation for 5min under rated load: ≤65K;
8. Device's own quality factor:Q≥10;
9. System measuring accuracy:virtual value 1.5 class;
10. Output power:single 220V,50Hz;
11. Over current, over pressure and flashover protection are provided for the testing object;
12. Environment temperature:-100C –50 0C
13. Relative humidity:≤90%RH,Altitude≤1000m;
III. Standards
GB10229-88 “Electric reactor TSCR”
GB1094 “Power transformer”
GB50150-2006 “Electrical equipment installation engineering electrical equipment handover test standard”
DL/T 596-1996 “Electrical equipment preventive test procedures”
GB1094.1-GB1094.6-96 “Enclosure protection class”
GB2900 “Electrotechnical terminology”
GB/T16927.1~2-1997 “High voltage test technique”
IV.Testing power and L、Cx
Testing object capacity range | Adjustable range of reactor |
0.08~0.2158uF | 47H~127H |
Comment:Cx is the capacity of testing object
Ac power frequency withstand test:The series resonance test device is used for the ac voltage withstand test of generator.
V. System configuration and parameters
1. Excitation transformer JLB-20kVA/5kV/0.4kV 1 set
a) Rated capacity:20kVA;
b) Input power:220V,single phase;
c) Output voltage:3kV
d) Type:Dry type
e) Weight: about 125kg;
f) Temperature rise of coil to air after
g) 1 min rated operation:≤65K;
2. Operating bench HZXB-(L)-20kVA/380V (Including voltage regulator) 1 Set
a) Rated capacity:20kVA;
b) Input voltage:380V
c) Output voltage:0~250V;
d) Protection function: zero, overcurrent, overvoltage and flashover protection;
e) Weight:about 100kg;
3. Adjustable reactor DK(L)-200kVA/50kV 1 Set
a) Rated capacity:200KVA;
b) Rated voltage:50kV;
c) Rated current:4A;
d) Adjustable inductance:47H~127H;
e) quality factor:Q≥10;
f) Type: Dry type, adjustable with iron core:;
g) Quantity:1 set;
h) Weight:about 180Kg ;
4. High voltage divider FRC-50kV 1 Set
a) Rated voltage:50kV
b) Testing accuracy:AC RMS 1.5 class;
c) Dielectric loss:tgσ≤0.5%;
d) The ratio of divided voltage:1000:1,accuracy:≤1.0%;
e) Weight:about 10Kg;
5. Compensating capacitor BC-50kV/0.08uF 1 Set
a) Rated voltage:50kV;
b) High voltage capacity:0.08uF
c) Weight:15kg
VI. System equipments List
List of equipment configuration
No. | Name | Model | Unit | quantity | Comment |
1 | Excitation transformer | JLB-20kVA/5kV/0.4kV | set | 1 | |
2 | Control Bench | HZXB-(L)-20kVA/380V | set | 1 | |
3 | Adjustable reactor | DK-(L)-200kVA/50kV | set | 1 | |
4 | Divider | FRC-50kV | set | 1 | |
5 | compensating capacitor | BC-50kV/0.08uF | set | 1 | |
6 | Testing Line | set | 1 |