HZDZ-S3 Portable Three Phase  Power Quality Analyzer
HZDZ-S3 Portable Three Phase Power Quality Analyzer

I.Product Description

Power quality refers to the quality of the AC power supply via the utility grid to the user, which normally means the good or bad situation of the electric energy in transmission line. Power quality problems are mainly caused by the load side of the terminal. For example, impact reactive load will lead to serious fluctuates to power network voltage, and decrease the quality of power supply.

    With the development of power electronics technology, on one hand, it brought positive side to the modern industrial energy efficiency and energy conversion. On the other hand, while the power electronic devices are widely used in all walks of life, it also has brought new and more serious damage to the power quality, and has become the main source of harmonic in grid.

    The increasing use of rectifiers, frequency control devices, electric arc furnaces, electric railway and a variety of power electronic devices in each distribution system, impact the electricity network or called power pollution. It causes voltage instability, over-voltage, generates harmonics and so on. Harmonic makes efficiency of electricity production, transmission and utilization reduce, so that the electrical equipment will be overheat, vibration and making noise, and insulation aging, shortened life expectancy, and even failure or burned. Harmonics can also cause localized power system an occurrence or series resonant parallel resonance, so that the harmonic content is amplified, resulting in capacitors and other equipment destroyed.

   Electrical properties of non-linear, impact resistance and unbalanced of these kind of load, causes serious pollution to the quality of power supply. Thus, eliminating the higher harmonic problem in supply and distribution system has a very positive meaning in improving the power quality issues and ensuring power system security, stability and economic operation.

   On the other hand, electrical equipments in modern industrial, commercial and residential users are more sensitive to power quality, and have a higher requirement of quality of power supply. Currently, harmonics, electromagnetic interference, power factor reduction have been tied to the three hazard of the power system.

   When it is interfered or contaminated, grid power quality can’t reach the national standards, so it has to be targeted on the grid power quality improvement. To understand the actual situation of power quality, you must have the appropriate equipment to test and analysis the actual situation. Counter the domestic condition, our company developed the professional power quality analysis instrument, which is suitable for the country. The following will illustrate the specific performances, parameters, methods of use on the power quality analyzer in detail.

II Technical Specifications

1. Input characteristics

  Voltage measuring range: 0~200V~800V, automatic cutting gear.

  Current measurement range

         Clamp transformers (three types): 5A / 25A (standard)

                                     100A / 500A (optional)

                                     400A / 2000A (optional)

  Phase angle measuring range: 0 ~ 359.99 °.

  Frequency measurement range: 45 ~ 55Hz.

  Voltage channels: three-channel (UA,UB,UC).

  Current channels: three-channel (IA,IB,IC).

  Maximum harmonic analysis times: 63 times.

  Maximum continuous storage period in 1 minute interval: 18 months.

2. Accuracy

  Measurement of electrical parameters section:

         Voltage: ± 0.2%

         Frequency: ± 0.01Hz

         Current, power: ± 0.5%

         Phase: ± 0.2 °

  Power quality section:

         Fundamental voltage tolerance: ≤0.5% F.S.

         Fundamental current tolerance: ≤1% F.S.

         Phase between fundamental voltage and current measurement error: ≤0.2 °

         Percentage of harmonic voltage measurement error: ≤0.1%

         Percentage of harmonic current measurement error: ≤0.2%

         Three phase voltage unbalance error: ≤0.2%

         Voltage deviation error: ≤0.2%

         Voltage fluctuation error: ≤0.2%

3. Working temperature: -10  ~ + 40  

4. Charging Power: 220V AC, 45Hz-55Hz frequency

5. Host Power: ≤3VA

6. Battery maximum working time: ≤10 hours

7. Insulation:

  1) The insulation resistance between the voltage, current input terminal and the housing ≤100MΩ.

  2) Withstand 1.5KV (valid value) with power frequency on operating power input and the shell, which lasts one minute.

8. Size: 320mm × 240mm × 130mm

9. Weight: 2.0Kg