I.Feature
High-voltage insulation resistance tester, with 5 range: 500V, 1000V, 2500V, 5000V, 10000V, test up to 20TΩ,there is also a manual boost function.
● design in strict accordance with safety standards
● insulation resistance range: 20t Ω @ 10KV
● the short-circuit current can be adjusted up to 3mA.
● automatically display the test values of polarization index (PI), absorption ratio (DAR), leakage current and capacitance, dielectric discharge test (DD) and step voltage test (SV).
● excellent anti-interference performance. When the interference current reaches 2mA, the instrument still ensures the test accuracy.
● AC and DC voltage test function of the tested line to automatically identify AC or DC.
● the capacitive test object discharges rapidly. During cable test, there is no need for manual discharge, and the instrument discharges rapidly automatically.
● two power supply modes: Powered by lithium battery, the endurance time can reach 6 hours.
At the same time, it can be charged in use. In case of power failure, it can automatically convert from AC power supply to battery power supply.
● the operation is simple and clear, and the insulation resistance analog column can be displayed.
● digital filtering function. When the displayed value deviates due to external influence, the filtering function is used to reduce the influence.
● perfect protection function and prompt function for fuse burnout.
● data saving function and data export.
II.Specification Parameter
● Safety specifications
IEC 61010-1 cat.iv 600V pollution degree 2
IEC 61326 EMC specification: electrical equipment for testing, control and inspection
IEC60529 IP64 (closed state of outer box)
● AC power supply: 120V ± 10%, 50 / 60 Hz, 20 VA
● battery power supply: 16.8v lithium ion battery
● battery life: 5000V@100M , about 6 hours
● dimensions (L x W x H): 32cm x 27cm x 14cm
● weight: 3.8kg
● output voltage accuracy: 100% to 110% of nominal value
● output voltage monitoring accuracy: ± 5% ± 10V
● voltage measurement range: AC: 30-600v (50Hz / 60Hz), DC: 30-600v
● voltage measurement accuracy: ± 2% ± 3dgt
● current test range: 10mA
● current measurement accuracy: 5% + 0.2na
● short circuit current: 2 to 5mA, adjustable output
● capacitance test range: 25uf
● capacitance test accuracy: ± 10% ± 0.03uf
● discharge rate of capacitor test object: from 5000v to 10V, 1s / µ F
● protection: 2% error, shielding 500K Ω leakage resistance under 100m Ω load
● analog display range: 100k Ω to 10t Ω
● digital display range: 10K Ω to 20t Ω
● insulation alarm: 0.01M Ω to 9999.99m Ω
● insulation resistance test range and accuracy (temperature: 23 ± 5 º C, relative temperature: 45 – 75% RH)
range accuracy | 500V | 1000V | 2500V | 5000V | 10000V | Other voltages |
Not specified | <100K | <100K | <100K | <100K | <100K | Range: 1G/ V, 100G at 100V. When the voltage is less than 200V, the resistance error increases by 10% |
±5%rdg±3dgt | 100K -100G | 100K-200G | 100K-500G | 100K-1T | 100K-2T | |
±20%rdg | 100G-1T | 200G-2T | 500G–5T | 1T-10T | 2T-20T | |